Short-Circuit Study

We calculate three-phase and single-phase fault current levels at every bus of the facility, check equipment withstand and breaking capacity against them, and deliver the results as the input of the protection coordination and arc flash studies.

GridTransformerMain busFault pointMMotorPVBESS
Schematic single-line: the power system model the study runs on. It does not represent a real facility.

Which questions does this study answer?

The short-circuit study is the foundation of power systems work: every later layer rests on its results.

  • Do my devices withstand the fault current?

    The short-circuit withstand and breaking capacities of switchgear, busbars, cables and breakers are compared with the calculated maximum fault currents.

  • How do levels change when the plant or grid changes?

    Changes such as a new transformer, generator, motor load or a solar/BESS connection are added to the model as scenarios and the fault current contributions are compared.

  • Is the minimum fault current enough for protection?

    Maximum and minimum fault scenarios are calculated together; at the minimum level, protection device sensitivity is noted for the coordination study.

  • Which other studies use the results?

    The bus fault currents are the direct input of the protection coordination and arc flash studies.

Required data

The more complete the data, the more reliable the model; missing items are listed at the start of the study.

  • Single-line diagram
  • Short-circuit power at the grid connection point (as notified by the utility)
  • Transformer, generator, motor and cable data (rating, impedance, length)
  • Existing protection device information
  • Planned changes (new transformer, solar, BESS, motor)

Working steps

The steps are sequential: the output of each is the input of the next.

  1. 01

    Data collection and single-line verification

    Data is collected; inconsistencies between the single-line diagram and equipment data are flagged.

  2. 02

    Model setup

    The grid, transformer, cable, motor and generator contributions are built in a single power system model in ETAP.

  3. 03

    Maximum and minimum fault scenarios

    Three-phase and single-phase fault currents are calculated for every bus under maximum and minimum operating conditions.

  4. 04

    Equipment check

    The calculated levels are compared with equipment withstand and breaking capacity; items that fall short are flagged.

  5. 05

    Reporting

    Results are delivered, document-controlled, together with their assumptions and limitations.

Reference standard

The calculation method rests on the framework below. It is a reference framework, not a certification or accreditation statement.

IEC 60909
Short-circuit currents in three-phase a.c. systems

Calculation software: ETAP

Delivered documents

  • Bus-by-bus fault current table (maximum and minimum)
  • Equipment withstand and breaking capacity check table
  • Statement of assumptions and limitations
  • Document control record (prepared by / checked by / approved by, revision)

Scope and limits

  • Results depend on the data taken from the facility and the grid short-circuit power notified by the utility; if the data changes, the study must be updated.
  • The calculation method is limited to IEC 60909; transient (EMTP) analyses are outside this scope.
  • The study is an engineering analysis; equipment replacement and field implementation are a separate scope.

A short-circuit study is not by itself a protection setting proposal; setting proposals are the subject of the protection coordination study.